IG-541 is a clean, inert gas suppression agent that suppresses fire through a physical mechanism. It is a precisely blended mixture of three naturally occurring atmospheric gases:
Nitrogen (N₂): 52%
Argon (Ar): 40%
Carbon Dioxide (CO₂): 8%
This agent is recognized globally as a safe and highly reliable solution for protecting high-value and mission-critical assets.
Inherently Safe for Occupants:
Upon discharge, it lowers the oxygen concentration in the protected enclosure from 21% to the designed suppression level (typically between 12.5% and 14%). This level is breathable and supports life, similar to the air at a high altitude, but effectively suppresses combustion.
The inclusion of CO₂ (8%) is critical as it stimulates breathing and prevents the risk of hypoxia in the oxygen-reduced atmosphere.
Zero Environmental Impact:
Ozone Depletion Potential (ODP) = 0
Global Warming Potential (GWP) = 0
Atmospheric Lifetime = 0
Composed of natural gases, it has no negative impact on the atmosphere.
Clean and Non-Damaging:
Suppression is purely physical. The agent does not undergo any chemical decomposition during discharge.
No residue is left behind, ensuring no damage to sensitive electronics, server hardware, historical documents, or valuable artwork.
Highly Effective and Reliable:
Achieves the design concentration typically within 60 seconds, ensuring rapid fire knockdown.
Simple system architecture with robust components, ensuring ease of maintenance and high reliability.
IG-541 operates on the principle of oxygen dilution (physical suppression).
When a fire is detected, the system is activated, and the IG-541 agent is discharged into the protected hazard. It works by introducing a sufficient quantity of inert gas to reduce the oxygen concentration below the level that supports combustion (typically below 15%). At the design concentration, the atmosphere will not support a flame, but remains safe for occupied spaces for a short period, allowing for safe evacuation.
Crucially: IG-541 is chemically inert and does not interfere with the fire's chemical chain reaction.

Agent Storage Pressure | 20 MPa(20℃) |
Maximum Operating Pressure | 23.2 MPa(50℃) |
Agent Charging Density | 0.28106 kg/L |
Operating Activation Power Supply | ≥DC24V,1.5A |
Fire Suppression Method | Total Flooding |
Agent Discharge Time | ≤60 S |
Activation Methods | Automatic, Manual, Mechanical Emergency Operation |
Pilot Gas | Nitrogen |
Pilot Gas Charging Pressure | 6 MPa(20℃) |
Operating Ambient Temperature | 0 ℃ ~ 50 ℃ |
The IG-541 system is the ideal choice for protecting:
Data Centers & Server Rooms
Telecommunication Switch Rooms
Power Control Rooms & Substations
Cultural Heritage Sites & Museums (Archives, Art Repositories)
Control Rooms on Offshore Platforms & Marine Vessels
Industrial Process Control Rooms
Bank Vaults & Record Storage Facilities
In summary, any water-sensitive, high-value, or irreplaceable asset within an enclosed space is a prime candidate for IG-541 protection.
Call to Action:
Are you looking for a fire suppression solution that provides superior protection for your critical assets while prioritizing human safety and environmental responsibility?
The IG-541 Inert Gas System is your answer. Contact our engineering and sales team today for a project-specific design proposal and quotation.
Streamlined Steps to Obtain Your Custom Fire Protection Solution
Liaoyepo Road, Ningxiang High-tech Zone, Changsha City,Hunan Province, China
Your full-cycle fire protection partner. We handle everything from concept and installation to long-term safety assurance.
Other fire suppression systems you might be interested in
Fill out the form below and our team will contact you shortly
Get a free design consultation with our expert engineers.